Sunday, July 5, 2020

33 KV Line Single Pole Erection Work with material Details.

33 KV Line Single Pole  Erection work necessary Process follow for Erection of 33 KV Line Single Pole .
1- After Survey Done  ,BOQ Prepartion  & Approval  BOQ of  Feeder Separation, Feeder Bifurcation  Then work Started Particular Locations.
2- For Erection of 33 KV Line Pole is necessary part.
3- Rural Project for 33 KV Line- 9.1 Mtr(280 kg) Long PCC Pole used.
 - Urban Project for 33 KV Line - 13 Mtr(37.1 kg/Mtr)  H-Beam Pole used.
4- Tractor mounted Pole pit digger &  Manually( By Labour) Pit digging done.
3- Pit hole done by Tractor mounted Pole pit digger & Erected The Pole .
4- During  Erection of Pole  Full Concerting (mixture of material   - 1:3:6  Cement: Sand: Aggregate) fill at  Pit hole in Rural Project .
For Urban Project  Pit hole Full Concerting with Composition ( 1:3:6 Cement:sand: Aggregate)  done from Bottom of pit hole to ground level.
5- V - Cross arm & V Cross arm supporting  Back Clamp( Angle 75*75*6 mm)  fitted in Pole work done during Erection of 33 KV Line.
6- Pole Top portion one Top Clamps done.
7- Three no. Pin insulator 10 to 15 KN  done ( Two pin insulator at V - Cross arm & one pin insulator at Top Clamps).
Note - Some urban  project no Top clamp used.
8- one no. Earthing Coil done.
9- Earthing for PCC Pole done as per approval.
10- Barbed wire (3.5 kg 12 SWG or 14 SWG GI Wire used as per approval).
11- Danger Board of 33 KV uesd in pole for indicate 33  KV Line Erected & it is Danger.
12- Stay Set 20 mm complete with Turn buckle work done.
13- Stay wire 8.5 kg per Stay set.
4- Stay Pit digging & Concerting work necessary for Erection Stay set with Stay wire.
15- Galvanised Nut, Bolt & Washer used.



https://youtu.be/VnpcEn--j9g